Wire gauge and fuse chart for 12 V and 24 V

Find your current down the left and your cable length across the top. The fuse is the same at any length; the wire gets thicker as the run gets longer.

Updated October 22, 2026. Prices checked on the makers' own sites that day.

How to read it

Amps are the continuous current of the device on that cable (watts divided by volts). Length is one way, battery or bus bar to device. Gauges are AWG, copper, 105°C insulation. "1/0" and up are written as such.

12 V chart

12 V DC: fuse and minimum wire gauge (AWG) by continuous amps and one-way length
AmpsFuse3 ft5 ft10 ft15 ft20 ft25 ft
5 A7.5 A141414121210
10 A15 A1414121088
15 A20 A141210866
20 A25 A14128664
30 A40 A10106442
40 A50 A886422
50 A70 A664221
60 A80 A664211/0
80 A100 A44211/02/0
100 A125 A2221/02/03/0
125 A175 A1/01/01/02/03/04/0
150 A200 A1/01/01/03/04/0Split it
200 A250 A3/03/03/04/0Split itSplit it
250 A350 ASplit itSplit itSplit itSplit itSplit itSplit it

24 V chart

24 V DC: fuse and minimum wire gauge (AWG) by continuous amps and one-way length
AmpsFuse3 ft5 ft10 ft15 ft20 ft25 ft
5 A7.5 A141414141414
10 A15 A141414121210
15 A20 A14141210108
20 A25 A1414121088
30 A40 A101010866
40 A50 A888664
50 A70 A666644
60 A80 A666442
80 A100 A444422
100 A125 A222221
125 A175 A1/01/01/01/01/01/0
150 A200 A1/01/01/01/01/02/0
200 A250 A3/03/03/03/03/03/0
250 A350 ASplit itSplit itSplit itSplit itSplit itSplit it

"Split it" means even 4/0 cable can't carry that current safely in a bundle: use two parallel runs, a higher system voltage, or have an installer design it.

Inverter cable sizes

Inverters are the biggest draw in most rigs. These assume a 4 ft run and the inverter at full output with a low battery (90% efficient at 12.0 V or 24.0 V).

Inverter battery cable and fuse, 4 ft one-way run
InverterCurrentFuseCable
1,000 W at 12 V93 A125 A2 AWG
1,000 W at 24 V46 A60 A6 AWG
1,500 W at 12 V139 A175 A1/0 AWG
1,500 W at 24 V69 A100 A4 AWG
2,000 W at 12 V185 A250 A3/0 AWG
2,000 W at 24 V93 A125 A2 AWG
3,000 W at 12 V278 A350 ASplit the run or go 24 V
3,000 W at 24 V139 A175 A1/0 AWG

The method

  1. Fuse. Take the continuous current and multiply by 1.25 (so the fuse carries no more than 80% of its rating), then round up to a standard size. Blue Sea Systems explains why a fuse shouldn't run at its full rating for long.
  2. Heat. Pick the thinnest wire whose ABYC E-11 rating, for up to three conductors bundled or in conduit with 105°C insulation, is at least the fuse size. That way the fuse always blows before the wire overheats.
  3. Voltage drop. Check the round trip with ABYC's formula (circular mils = 10.75 x amps x round-trip feet / allowed volts drop) and keep it under 3%. If that needs thicker wire, use it.
  4. Minimums. Nothing thinner than 14 AWG for a fused branch, nothing thinner than 4 AWG for a battery main.

Runs through the engine bay (alternator to DC-DC charger) use ABYC's lower engine-room rating. The planner and the wiring tool apply exactly this method to your own lengths.

ABYC ampacity table we use

Allowable amps, copper, 105°C insulation (ABYC E-11 Tables VI-A and VI-B)
Wiremm²Bundled (up to 3)Bundled, engine roomSingle, free airMax 12 V run at rating, 3% drop
16 AWG1.318 A15 A25 A2.4 ft
14 AWG2.125 A21 A35 A2.8 ft
12 AWG3.332 A27 A45 A3.4 ft
10 AWG5.342 A36 A60 A4.1 ft
8 AWG8.456 A48 A80 A4.9 ft
6 AWG13.384 A71 A120 A5.2 ft
4 AWG21.2112 A95 A160 A6.2 ft
2 AWG33.6147 A125 A210 A7.6 ft
1 AWG42.4172 A146 A245 A8.1 ft
1/0 AWG53.5200 A170 A285 A8.8 ft
2/0 AWG67.4231 A196 A330 A9.6 ft
3/0 AWG85.0270 A229 A385 A10.4 ft
4/0 AWG107.2312 A265 A445 A11.4 ft

Fuse type matters near a lithium battery

A lithium bank can push thousands of amps into a dead short. Put a fuse rated to interrupt that, such as a Class T, within 7 inches of the battery positive. Blue Sea Systems' figures show ANL fuses only blow at about 140% to 266% of their rating, so size an ANL by its blow point, not its label.

Safety first

Fuse every positive wire as close to the battery or bus bar as you can, and use the wire and fuse sizes from a standard table, not a guess. Boats should follow ABYC E-11; anything that touches 120/240 V AC should follow the NEC. Have a qualified installer check any 120/240 V AC or shore power work.

Questions people ask

What size wire for a 2,000 W inverter at 12 V?

A 2,000 W inverter can pull about 185 A from a 12 V battery. With a 4 ft run that's 3/0 AWG copper on a 250 A fuse by our method. At 24 V the current halves and so does the cable size.

Should the fuse match the wire or the device?

The fuse protects the wire. It must be no larger than what the wire can carry, and large enough that the device's normal current stays under 80% of the fuse rating. When the device maker specifies a fuse, use that size or smaller, as long as the wire can carry it.

Why is this chart thicker than the one that came with my inverter?

Many charts use free-air ratings and allow 10% voltage drop. We use ABYC's rating for wires bundled or in conduit (how they run in a van wall) and hold drop to 3%. Thicker cable runs cooler and wastes less energy; on short runs the cost difference is small.

Is length one way or round trip?

The chart's lengths are one way: from the battery or bus bar to the device. The math doubles it, because current flows out on the positive and back on the negative.

Does the negative wire need to be the same size?

Yes. The negative carries the same current back to the battery, so it gets the same gauge as the positive.